225KVA single-phase oil-immersed transformers roll out of the GUANGBIAN plant in China every week. They take 11KV to 33KV down to 0.4KV for solar sites, factory loads, and village grids.
● 15,000 sqm plant. 3,000+ transformers roll out a year.
● Custom ratios and tap changers: yes, send the data.
● Lead time runs 25-30 days. 15-20 when parts sit on the shelf.
● Spare parts in stock, not on backorder.
This 225KVA single-phase oil-immersed transformer comes from the GUANGBIAN factory in China. Feed it [11/19/33]KV, it hands back 0.4KV. Sealed tank design, cold-rolled silicon steel core, oxygen-free copper windings. Every unit tested before shipping.
Materials & Construction
● Core: cold-rolled grain-oriented silicon steel, full-miter joints, no punched holes—lower no-load loss
● Windings: oxygen-free copper, runs cooler
● Tank: corrugated or expansion type, fully sealed
Sealed means the oil never meets air. Clean oil ages slower. That's why these units last 25+ years with yearly checks. No conservator also cuts height—fits tight installations.
Technical Specifications
1. PRODUCT IDENTIFICATION
Product Name
Oil-Immersed Power Transformer
Type & Size
D-M-225/19
Phase
Single-phase (1 φ)
Rated Capacity
225
kVA
Frequency
50
Hz
Voltage Combination
19 / 0.4
kV
Connection Symbol
II0
Rated Current
11.84 / 562.5
A
HV / LV
Cooling Type
ONAN
2. RATING & TAPPING RANGE
Tap Position
HV Voltage (V)
HV Current (A)
LV Voltage (V)
LV Current (A)
1
19950
2
19475
3
19000
11.84
400
562.5
4
18525
5
18050
3. ROUTINE TEST RESULTS
3.1 Measurement of Voltage Ratio & Check of Connection Symbol
Tap Position
Voltage Ratio
Measured Error (%)
Connection Symbol
1
49.8750
0.03
2
48.6875
0.05
3
47.5000
0.04
II0
4
46.3125
0.04
5
45.1250
0.04
3.2 Measurement of Winding Resistance (ambient 10 °C)
Winding
Tap Position
Resistance (Ω)
HV (A–X)
1
9.981
HV (A–X)
2
9.729
HV (A–X)
3
9.472
HV (A–X)
4
9.236
HV (A–X)
5
8.967
LV (a–x)
—
0.003358
3.3 Measurement of Insulation Resistance
Measurement
Result
HV – (LV + Earth)
2000
MΩ
LV – (HV + Earth)
1500
MΩ
3.4 Insulating Oil
Item
Result
Oil type
25# mineral oil
Breakdown voltage
40
kV
3.5 Separate-Source Voltage Withstand Test (applied voltage)
Measurement
Power Frequency
Voltage
Duration
HV – (LV + Earth)
50 Hz
50 kV
60 s
LV – (HV + Earth)
50 Hz
5 kV
60 s
3.6 Induced Overvoltage Withstand Test
Applied at
Frequency
Test Level
Duration
LV side
100 Hz
200 % rated voltage
60 s
3.7 Measurement of No-Load Current & No-Load Loss
Item
Result
No-load current
0.62
%
No-load loss
310
W
3.8 Measurement of Short-Circuit Impedance & Load Loss (measured at 10 °C, referred to 75 °C)
Tap Position
Impedance Voltage at 75 °C
Load Loss at 75 °C
3
3.56 %
3120 W
3.9 Seal Test
Item
Result
Tank seal test
15 kPa applied for 24 hours — no leakage
Where It Fits
Solar + diesel microgrids, rural distribution, factory loads, street lighting. Handles load swings between sources without complaint. One 225KVA transformer powers roughly 100-180 households at 220V.
FAQ
Custom ratio?
Yes, send your nameplate data.
Lead time?
25-30 days standard, 15-20 if parts in stock.
Maintenance?
Once a year—oil check, tighten connections, clean bushings.
About GUANGBIAN
15,000 sqm factory, core processing to final test under one roof. ISO 9001:2015, IEC 60076 compliant. Every unit passes four checks before it ships. Export-grade wooden cases, 20/40ft containers, own crane crew.
Send specs and destination port. Quote within 24 hours.
For inquiries about Oil Immersed Transformer, Dry Type Transformer, Pole Mounted Transformer or price list, please leave your email to us and we will be in touch within 24 hours.